    Computer aided-program for validation of measuring system from unit step response by time convolution method
    (2005-01-01)
    Yutthagowith, P.
    ;
    Pattanadech, N.
    ;
    Kunakorn, A.
    ;
    Phoomvuthisarn, S.
    This paper presents the design and development of the computer algorithm based on LabVIEW for verification of a high voltage measuring system. The algorithm consists of two parts. The first part is a program for calculating the parameters of unit step responses which are verified an ability of the measuring system by a comparison with the values given in IEC 60060-2. The second part is a program for calculating the output voltage waveform by time convolutions between standard testing waveforms and unit step responses. The standard waveforms under investigation are full lightning impulse voltage waveforms, tail-chopped lightning impulse voltage waveforms, front-chopped lightning impulse voltage waveforms and steep-front voltage waveforms according to IEC standards 60060-2 and 61211. This paper considers two different types of the measuring systems, with a resistive voltage divider and a damped capacitive voltage divider for testings. The results show that the algorithm proposed in this paper is practicable, and should be a useful tool for impulse voltage measurements in a standard high voltage laboratory.