Kunakorn, Anantawat
Loading...
Preferred name
Kunakorn, Anantawat
Alternative Name
Kunakorn, A.
Kunakorn, Anatawat
Main Affiliation
Email
anantawat.ku@kmitl.ac.th
2 results
Now showing 1 - 2 of 2
- Some of the metrics are blocked by yourconsent settings
Item type:Publication, Dielectric Response Analysis on Artificial ZnO Surge Arrester Degradation Using Polarization and Depolarization Current Based Method(2024-01-01) ;Chuayin, Chaitawat; ;Zinck, Matthieu ;Methavithit, WinaiSuksagoolpanya, SuthatThis paper presents an alternative method to investigate the problems of surge arrester based on dielectric response analysis. The study is made using a 21-kV, 25-kA station class surge arrester to be test specimens, the former Zinc Oxide (ZnO) varistors inside were removed and replaced with artificial degraded ZnO varistors (impulse ageing, tracking problems, moisture ageing under wet and dry condition and cracking ZnO varistors). The experiments are carried out by Polarization and Depolarization Current (PDC) measurement. The test result analyses were proposed in terms of both the time domain and frequency domain. The measurement results show significant differences in dielectric response characteristics between healthy surge arresters and aged surge arresters. In addition, the dielectric response analysis tends to characterise the problems of surge arrester i.e., conduction problems and polarization problems which will be further discussed in this paper. - Some of the metrics are blocked by yourconsent settings
Item type:Publication, The Effect of Electrical and Moisture Degradation of Metal Oxide Varistor with Insulation Diagnosis(2020-10-25) ;Chuayin, Chaitawat ;Zinck, Matthieu; Condition based monitoring of surge arresters (SA) has become a primary concern to ensure power supply quality on medium and high voltage networks. Understanding of SA behavior helps forecast their failure. This paper presents the analysis of dielectric response and conductivity of Metal Oxide Varistor (MOV) under degradation factors (normal ageing, impulse ageing and moisture ageing) using Polarization and Depolarization techniques. Normal ageing is represented by stressing the MOV with 115°C temperature. For impulse ageing, 20, 40 ,60 and 100 shots of positive and negative polarity of standard lightning impulses current were applied. Moisture ageing was performed by soaking MOV under 115°C temperature for 12 hours representing wet condition and the soaked blocks were left at room temperature for 24 hours representing dry condition. Polarization and Depolarization Current (PDC) was measured after each ageing step. Resistivity, conductivity and polarization index were interpreted for insulation diagnosis. The experiments were taken on the MOV with rated voltage 3 kV and 5kA-nominal discharge. The importance of nondestructive electrical diagnostics based on polarization methods is validated by test results and is highlighted in detail in this paper. Finally, the results of different ageing factors were compared and discussed.
