  4. Dielectric Response Analysis of Mineral Oil Immersed Transformer Insulation during Manufacturing Process
Loading...
Thumbnail Image

Dielectric Response Analysis of Mineral Oil Immersed Transformer Insulation during Manufacturing Process

Author(s)
Nganpitak, Tritod
Nimsanong, Phethai
Maneerot, Sakda
Pattanadech, Norasage
Date Issued
June 1, 2019
Type
Conference Paper
DOI
10.1109/ICDL.2019.8796642
Abstract
Polarization and Depolarization current (PDC) method is one of non-destructive insulation testing methods that can be used for diagnosis the insulation conditions of high voltage equipment. This paper presents the PDC analysis of an oil immersed distribution transformer measured during the manufacturing process. A 22 kV, 30 kVA single phase transformer was designed and constructed. During manufacturing process, the polarization current and depolarization current of the transformer insulation were measured for 6 case studies as follows: 1) paper insulation between iron core and low voltage (LV) windings before dry and vacuum in the oven, 2) paper insulation between LV and high voltage (HV) windings before dry and vacuum in the oven, 3) paper insulation between iron core and LV windings after dry and vacuum in the oven, 4) paper insulation between LV and HV windings after dry and vacuum in the oven, 5) oilpaper insulation between iron core and LV windings after dry and impregnation process and 6) oil-paper insulation between LV and HV windings after dry and impregnation process. Then, PDC test results were analyzed. It was found that the moisture content in the paper insulation clearly affected the capacitance at power frequency, and PDC shapes. Besides, the impregnation process had a good effect on the capacitance ratio and dielectric dissipation factor. Moreover, the current difference of dry paper insulation between HV and LV windings presented the nonlinear characteristic both before and after impregnation process.
Citation
Proceedings IEEE International Conference on Dielectric Liquids, 2019-June, 2019
Subjects

Depolarization curren...

Dielectric response a...

Mineral oil

Oil-paper insulation

Polarization current

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback