The Impact Study of Electrical Vehicle Charging Stations Loading to Thailand’s Northeast Power System and DRG Integration Planning to Reduce Power Congestion

Author(s)
Wannoi, Narumon
Wannoi, Chaisit
Chompooin-inwai, Chai
Jirasuwankul, Nirudh
Boonkhun, Churirat
Date Issued
January 1, 2023
Type
Article
DOI
10.22266/ijies2023.0430.46
Abstract
This article presents the impact study of electrical vehicle charging stations (EVCS) loading to the Thailand’s North eastern power system. Main purposes of this paper are to find the maximum number of EVCS that can be loaded to power system and to rank the critical areas under EVCS load changing by using the repeated power flow calculation technique. Results from the calculation are for the integration planning of distributed renewable generators (DRG) to reduce system congestion. Typically, the critical areas are buses or devices that violate of system control limits. The system control limits are consisting voltage limit and load percentage limit of power transfer devices. All critical areas are needed to improve system stability and reduce system congestion for support the EVCS growing. In this study, The EVCS have been installed on main roads in Thailand’s North-eastern area from Bangkok to Nong-Khai province with a length of 624 km. The EVCS were installed every 50 km, totally 11 stations, and connected to 115 kV substations in the system. The impact study results found that the system experienced with congestion problem on following elements: a) 11 critical buses at 115kV network, b) one critical bus at 230kV network and c) one transmission line is overload to 100 percent at 115kV network when each of EVCS station load increase to 30 MW. In addition, study results reveal that when installed DRG at the right and proper locations, these can reduce congestions situation, reduce system losses and enhance system stability
Citation
International Journal of Intelligent Engineering and Systems, 16(2), 561-570, 2023
Subjects

Distributed renewable...

Electrical vehicle ch...

Power congestion

Repeated power flow c...

Violation limit

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback