Abstract

The main objective was to evaluate cyclic efficiency of a multilayer desiccant bed column. The experimental setup consisted of an air humidifier unit, a heating unit for regeneration, and the desiccant bed column with 15 layers. An airflow rate of 2.4 m3/min with the humidity ratio of 20 g water/kg dry air was used in this study. The results showed that the highest dehumidification rate of 21 g water/min was found at the beginning of the dehumidification process. During the regeneration process, the highest regeneration rate was 39 g water/min when regenerating the desiccant at a temperature of 90°C. For cyclic operation process, the cyclic efficiencies were 11% and 7% at the regeneration temperatures of 70°C and 90°C, respectively. The cyclic efficiency was dependent on the regeneration temperature.

Description

Keywords

Citation

E3s Web of Conferences, 187, 2020