Partial discharge inception voltage investigation of mineral oil: Effect of electrode configurations and oil conditions

Author(s)
Pattanadech, N.
Muhr, M.
Date Issued
October 1, 2016
Type
Article
DOI
10.1109/TDEI.2016.7736853
Abstract
The aim of this paper is to describe the Partial Discharge Inception Voltage (PDIV) and Partial Discharge (PD) characteristic of mineral oil tested by various electrode configurations. Furthermore, mineral oil with different conditions was investigated under AC voltage. The PDIV and PD of the mineral oil, Nynas Nytro 4000x, with water content about 4 ppm was investigated by using various electrode configurations of needle - plane and needle - sphere electrodes under room temperature. The PDIV test circuit was set up according to IEC 60270. Then, two PDIV measurements were applied for the investigation. The first PDIV test procedure (IEC method) was performed in accordance with IEC 61294. The second PDIV test procedure so-called combined PDIV method was adapted from IEC standard. Moreover, the electric field distributions of the electrode systems were also calculated. According to the test results, PDIV depended clearly on the electric field stress of the electrode system and the test method. Compared with other electrode configurations, the 10 μm tip radius needle - 75 mm dia. plane electrode gave the highest electric field stress and inversely provided the lowest PDIV value tested by both test methods. The combined PDIV test method generated the PDIV, charge quantity, and charge repetition significantly lower than measuring by IEC method. To investigate the effect of oil conditions on PDIV and PD characteristics, the combined conditions of temperature and water content of the mineral oil were controlled as the parameters for investigation. It was found that the water content in the mineral oil influenced approximately on PDIV value when the oil temperature was at room temperature. However, at the oil temperature of 40-90 °C, the PDIV values of the mineral oil with water content 4, 20 and 40 ppm were relatively the same. From the PD pulse current test results, PD pulse current recorded at the PDIV value from both test methods was about 0.15-1.3 mA. Pulse duration was in the range of 0.7-9 μs and the rise time was between 40-570 ns.
Citation
IEEE Transactions on Dielectrics and Electrical Insulation, 23(5), 2917-2924, 2016
Subjects

charge quantity

mineral oil

partial discharge

Partial discharge inc...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback