  4. Studies of Electrical and Thermal Characteristics of Natural Ester Immersed Transformer Compared with Mineral Oil Immersed and Palm Oil Immersed Transformer
Loading...
Thumbnail Image

Studies of Electrical and Thermal Characteristics of Natural Ester Immersed Transformer Compared with Mineral Oil Immersed and Palm Oil Immersed Transformer

Author(s)
Maneerot, S.
Jariyanurat, K.
Nimsanong, P.
Bunlaksananusor, C.
Kunakorn, A.
Pattanadech, N.
Date Issued
November 14, 2018
Type
Conference Paper
DOI
10.1109/CMD.2018.8535807
Abstract
This paper represents studies of electrical and thermal characteristics of natural ester immersed transformer compared with mineral oil immersed and palm oil immersed transformer by designing and constructing three single-phase transformers with rated 400/1000V 10kVA, the first transformer used mineral oil, the second transformer used natural ester, and the last one used palm oil, for studying about electrical properties, thermal properties and chemical properties under different types of liquid insulation in each transformer. First of all, three types of liquid insulation were tested with many item such as dielectric breakdown strength according to IEC 60156, dielectric dissipation factor following to ASTM D924-99. Besides, dielectric breakdown strength of impregnated pressboard were also investigated following to IEC 60243-1. Moreover, the chemical properties of the insulations were tested for some properties such as moisture content in accordance with ASTM D1533-00, interfacial tension according to ASTM D0971-99, acidity according to ASTM D974-02. After that, transformers were operated at 100 % of designed rated with inductor load for four months by which the temperature, current, and voltage were recorded every hour. Every two months, the liquid insulation was sampling from each transformer to be investigated. From the test results, they can concluded that natural ester are the alternative liquid insulation for using instead of mineral oil. In part of palm oil, it has good properties but it has the weak points about dielectric dissipation factor and acidity which are higher than the others.
Citation
2018 Condition Monitoring and Diagnosis Cmd 2018 Proceedings, 2018
Subjects

electrical characteri...

immersed transformer

mineral oil

natural ester

palm oil

thermal characteristi...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback