  4. Failure analysis of dielectric of low voltage power capacitors due to related harmonic resonance effects
Loading...
Thumbnail Image

Failure analysis of dielectric of low voltage power capacitors due to related harmonic resonance effects

Author(s)
Boonseng, C.
Chompoo-inwai, C.
Kinnares, V.
Nakawiwat, K.
Apiratikul, P.
Date Issued
December 1, 2001
Type
Conference Paper
Abstract
This paper presents an investigation on the failure of low voltage power capacitors used in the textile industrial located on Thailand. The causes of the failure as well as the failure mechanisms of the dielectric used as the insulation of such capacitors are analyzed. It is found that the harmonic resonance can increase the current flowing through the capacitors. This result in the extra heat, generated inside the dielectric, which exceeds the level under the normal operation. Such heat results in the increase of the partial discharge inside the capacitors. This can eventually lead to the reduction of the lifetime of the capacitors.
Citation
Proceedings of the IEEE Power Engineering Society Transmission and Distribution Conference, 3(WINTER MEETING), 1003-1008, 2001
Subjects

Capacitor

Failure analysis

Harmonics resonance

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback