Advanced conceptual design for the regasification process to minimize carbon emissions, water use, and reduce operating costs for AI data centers, airport hubs, smart cities and initial zero-emission LNG receiving terminals

Author(s)
Sermsuk, Maytungkorn
Sukjai, Yanin
Rajoo, Srithar
Kiatkittipong, Kunlanan
Wiboonrat, Montri
Siripongdee, Surapong
Date Issued
June 1, 2026
Type
Article
DOI
10.1016/j.rineng.2026.111031
Abstract
Achieving net-zero greenhouse gas emissions by 2050 requires improving energy efficiency in transitional fuels such as liquefied natural gas (LNG). In 2023, global LNG imports reached 401.5 MTPA; however, most of the 180 LNG receiving terminals worldwide still discharge large amounts of recoverable cold energy into the ocean. Meanwhile, the rapid growth of artificial intelligence (AI) data centers is driving unprecedented electricity demand, with projected global electricity consumption exceeding 3000 TWh by 2030. This study proposes an advanced LNG regasification system integrating Intermediate Fluid Vaporization (IFV), Rankine Cycle (RC), and Direct Expansion Cycle (DEC) to recover both temperature and pressure exergy. The system is evaluated for LNG terminals with capacities of 10–30 MTPA under pressure levels of 70, 30, and 6 bar across eight operational models and two infrastructure configurations. Results indicate that terminal electricity imports are reduced by 52–78 % compared with conventional open rack vaporizer (ORV) systems. Net electricity generation ranges from 12.09 to 197.91 MW, while chilled water cooling capacity reaches 272.72–1075.44 MW. Cooling electricity demand is reduced by approximately 79 %, lowering data center Power Usage Effectiveness (PUE) from 2.00 to 1.36. Water Usage Effectiveness (WUE) decreases from 1.9 to 3.0 to approximately 0.3 L/kWh, achieving an 89–93 % reduction in cooling-related water use. At 30 MTPA, carbon emissions are reduced by up to 2.99 million tons annually, with economic savings of USD 119.96–603.15 million per year and a maximum IRR of 37.7 %. These results demonstrate the significant potential of LNG cold energy integration for near-zero-emission terminal operation and sustainable data center cooling.
Citation
Results in Engineering, 30, 2026
Subjects

Carbon emissions

Cold energy utilizati...

cold recovery

Data center

District cooling

Liquefied natural gas...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback