Ventilation improvement for effective protection of healthcare workers in negative pressure airborne infectious isolation room from viral aerosols

Author(s)
Kaeophet, Thanchanok
Dejchanchaiwong, Racha
Tekasakul, Perapong
Phonsahwat, Thongchai
Khongprom, Parinya
Ingviya, Thammasin
Kongkamol, Chanon
Morris, John
Date Issued
July 1, 2024
Type
Article
DOI
10.1016/j.buildenv.2024.111665
Abstract
A negative pressure airborne infectious isolation room (AIIR) is the primary healthcare air contamination control system used for the treatment of severe respiratory infectious patients. Effects of the ventilation system configuration and conditions on airflow pattern, aerosol distribution and ventilation performance were investigated using computational fluid dynamics (CFD). The field measurement by SARS-CoV-2 environmental surface test was also conducted. The cycle threshold values from transcription polymerase chain reaction (RT-PCR) method showed inverse relation to the simulated number of particles trapped on the surfaces indicating a good agreement. Modification of the present AIIR to have alignment between air inlet and outlet where the aspect ratio of the air outlet, Width (W): Height (H) = 1:1 (Improved case: IC#1) showed a 78 % reduction of aerosol concentration in healthcare workers (HCWs) zones. Aerosol concentrations were increased when the openings of the air outlet were enlarged. Addition of air outlet led to large swirling air, resulting in more aerosols being trapped and suspended in the air. Results suggested that AIIR with alignment air inlet on the ceiling and air outlet at the wall over the patient's head with W:H = 1:1 be the most suitable configuration to maximize the ventilation performance and minimize exposure risk to aerosolized viral infection for HCWs. Air change rate plays a more important role than the differential pressure on the removal efficiency. The differential pressure value should be at least −2.5 Pa and the air supply rate 12 ACH for effective protection of HCWs in the negative pressure AIIR.
Citation
Building and Environment, 259, 2024
Subjects

Aerosol

Airborne transmission...

CFD

Infectious respirator...

Negative pressure roo...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback