Loading...
Investigation of harmonic current of power system using static var compensator for grid-connected induction generators under condition of low wind speed
Author(s)
Sawetsakulanond, B.
Date Issued
January 1, 2014
Type
Conference Paper
Abstract
This paper presents the investigation of harmonic currents of a power system associated with a static Var compensator for grid-connected induction generators under condition of low wind speed. The static Var compensator uses fixed capacitor and thyristor controlled reactor. The investigation of reactive power compensation for 2.2 kW, 220/380 V, 8.5/5.2A, Δ/Y, 4 P, induction generator has been performed under low wind speed and constant power factor at 0.9. The obtained results can be guidelines for harmonic mitigation of reactive power compensation for grid-connected induction generators inside a nation.
Citation
2014 17th International Conference on Electrical Machines and Systems Icems 2014, 1406-1409, 2014