  4. An analysis of total loss and temperature of oil-immersed transformer with short circuit test linear load and non-linear load
Loading...
Thumbnail Image

An analysis of total loss and temperature of oil-immersed transformer with short circuit test linear load and non-linear load

Author(s)
Suechoey, B.
Tadsuan, S.
Khluabwannarat, P.
Chompoo-inwai, C.
Date Issued
January 1, 2005
Type
Conference Paper
DOI
10.1109/ipec.2005.206987
Abstract
This paper presents the measured temperature at top oil and on winding at high voltage part, low voltage part due to winding loss. By placing the thermocouples at the bottom, the middle and the top of mineral oil-immersed transformer, the variety winding temperatures are measured. The 3 - test conditions are 1. Short circuit test, 2. Linear load test and 3. Non linear load test. The temperature results show the difference temperature at any parts of the 10 kVA, 380V/220V, 3 phase, Dyn11 and ONAN ventilating transformer. The results of measured temperature will be compared with one another to get the difference temperature. If that temperature is higher than the rated temperature of insulator in transformer, its lifetime will be shorter. Finally, the result will be analysed about the relations among heat at any part and are useful for design, correction and protection of the transformer by heat.
Citation
7th International Power Engineering Conference Ipec2005, 2005, 2005
Subjects

Non-linear load

Oil-immersed transfor...

Total loss

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback