  4. Comparison of dissolved gases in natural ester under partial discharges
Loading...
Thumbnail Image

Comparison of dissolved gases in natural ester under partial discharges

Author(s)
Jongvilaikasem, Korraya
Maneerot, Sakda
Jariyanurat, Kittipod
Pattanadech, Norasage
Date Issued
June 1, 2019
Type
Conference Paper
DOI
10.1109/ICDL.2019.8796571
Abstract
Currently, natural ester is alternative liquid insulation applied for both distribution and power transformers. Generally, transformers are expected to operate stably and reliably. However, their functions may fail during operation. Dissolved gases analysis is one of the worldwide accepted diagnostic techniques to examine the insulation integrity of the transformers. This paper presents the analysis of dissolved gases generated from partial discharge (PD) experiments i.e. corona discharge, surface discharge and internal discharge which were conducted in the test cell filled with natural ester (FR3). To simulate corona discharge, a needle electrode with a tip radius of 10, 20, and 40 micrometers was used as high voltage electrode and the plane electrode with a diameter of 45 mm was used as a grounded electrode. The gap distance was fixed at 32 mm. The corona discharge experiment was performed for 2 hours at the test voltage level of 35, 40, 45 kV respectively. In case of surface discharge, the pressboard samples i.e. non-impregnated pressboards, 8-hour impregnated pressboards, and 16-hour impregnated pressboards were inserted between the 20-micrometer tip radius needle and grounded plane. Then, the test voltage of 25 kV was applied to the electrode system for 1 hour. Besides, the surface discharge was tested at 35 and 45 kV respectively. For internal discharge, the pressboard samples i.e. non-impregnated pressboards, 8-hour impregnated pressboards, and 16-hour impregnated pressboards were inserted between the plane-plane electrodes. Then the test voltage of 25 kV was applied to the electrode system for 1 hour. Moreover, the internal discharge was tested also at 35 and 45 kV. Their natural ester samples were sampling from the test cell for each experiment and the dissolved gases were measured and analyzed. From the test results, it was found that the types and quantity of dissolved gases depended strongly on the type of discharge and material samples.
Citation
Proceedings IEEE International Conference on Dielectric Liquids, 2019-June, 2019
Subjects

Corona discharge

Dissolved gases analy...

Internal discharge

Natural ester

Surface discharge

Transformer

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback