Uncertainty of fault location prediction due to behavior of simultaneous fault in electrical power system using travelling wave theory

dc.contributor.authorNgaopitakkul, A.
dc.contributor.authorApisit, C.
dc.date.accessioned2026-08-06T10:02:06Z
dc.date.available2026-08-06T10:02:06Z
dc.date.issued2011-04-01
dc.description.abstractThis paper presents uncertainty of fault location due to behavior of simultaneous fault in an electrical power transmission system. The fault signal is simulated using PSCAD/EMTDC. The Discrete Wavelet Transform (DWT) is used to detect the high frequency components. The variation of high frequency components of positive sequence current signals at the end of transmission line is considered. The results obtained from the analysis are used in order to locate faults with an application of travelling wave theory. It is found that the travelling wave theory cannot precisely locate simultaneous fault in an electrical power transmission system. © 2011 ISSN 2185-2766.
dc.identifier.citationIcic Express Letters Part B Applications, 2(2), 383-388, 2011
dc.identifier.issn21852766
dc.identifier.other2-s2.0-79952366265
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/3573
dc.sourceIcic Express Letters Part B Applications
dc.subjectFault location
dc.subjectSimultaneous fault
dc.subjectTravelling wave
dc.subjectWavelet transform
dc.titleUncertainty of fault location prediction due to behavior of simultaneous fault in electrical power system using travelling wave theory
dc.typeArticle