Evaluation of cyclic efficiency of multilayer desiccant bed column
| dc.contributor.author | Prueksa Sawardsuk | |
| dc.contributor.author | Jiraporn Sripinyowanich Jongyingcharoen | |
| dc.contributor.author | Ekkapong Cheevitsopon | |
| dc.date.accessioned | 2025-07-21T06:02:48Z | |
| dc.date.issued | 2020-01-01 | |
| dc.description.abstract | The main objective was to evaluate cyclic efficiency of a multilayer desiccant bed column. The experimental setup consisted of an air humidifier unit, a heating unit for regeneration, and the desiccant bed column with 15 layers. An airflow rate of 2.4 m 3 /min with the humidity ratio of 20 g water/kg dry air was used in this study. The results showed that the highest dehumidification rate of 21 g water/min was found at the beginning of the dehumidification process. During the regeneration process, the highest regeneration rate was 39 g water/min when regenerating the desiccant at a temperature of 90°C. For cyclic operation process, the cyclic efficiencies were 11% and 7% at the regeneration temperatures of 70°C and 90°C, respectively. The cyclic efficiency was dependent on the regeneration temperature. | |
| dc.identifier.doi | 10.1051/e3sconf/202018704018 | |
| dc.identifier.uri | https://dspace.kmitl.ac.th/handle/123456789/9027 | |
| dc.subject.classification | Adsorption and Cooling Systems | |
| dc.title | Evaluation of cyclic efficiency of multilayer desiccant bed column | |
| dc.type | Article |