Effect of the drop out fuse connection scheme on the overvoltage and the surge arrester in a distribution system

dc.contributor.authorChaiyaporn Lothongkam
dc.contributor.authorTheerasak Patcharoen
dc.contributor.authorSuntiti Yoomak
dc.date.accessioned2025-07-21T06:09:49Z
dc.date.issued2023-09-05
dc.description.abstractOvervoltage is a critical problem of Thailand' distribution system. The electrical protection device in the distribution system needs to be able to support this level of overvoltage. In the distribution system connecting the Chachoengsao2 substation and the Bang Khla substation, the overvoltage from a ferro resonance phenomenon affects the surge arrester directly. This research studies the effect of the drop-out fuse connection scheme on the voltage and surge arrester using the RMS/EMT Simulation mode in the DIgSILENT program. Normally, the surge arrester withstands a voltage of 1.9 p.u. of the phase voltage. If the overvoltage in the distribution system is higher than the voltage that the surge arrester can withstand, the surge arrester can be damaged. Therefore, it is necessary to study and analyze the drop out fuse insertion pattern that affects the overvoltage in the distribution system to understand the causes of overvoltage problems and their effects on each type of electrical protective equipment.
dc.identifier.doi10.1016/j.egyr.2023.08.058
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/12790
dc.subjectOvervoltage
dc.subjectSurge arrester
dc.subjectFuse (electrical)
dc.subjectVoltage drop
dc.subject.classificationLightning and Electromagnetic Phenomena
dc.titleEffect of the drop out fuse connection scheme on the overvoltage and the surge arrester in a distribution system
dc.typeArticle

Files