Design of Counterpoise Grounding Electrodes Encased with Low Resistivity Material for Transmission Towers

dc.contributor.authorSirachansawang, P.
dc.contributor.authorHorchue, T.
dc.contributor.authorYutthagowith, P.
dc.date.accessioned2026-08-06T10:24:38Z
dc.date.available2026-08-06T10:24:38Z
dc.date.issued2019-05-15
dc.description.abstractThis paper presents design of counterpoise electrodes encased with earthing enhancing compounds or more effective grounding (MEG) for transmission towers. Approach is based on a full-wave electromagnetic analysis. For counterpoise analysis, the partial element equivalent circuit (PEEC) is used. In this paper, we use lightning parameters from IEC 62305 as reference. For normal case, the soil ionization and frequency dependent parameters are ignored. In cases high ground resistivity more than 1000 ohm-meter, grounding of long counterpoise makes the capacitive result, this make electrode impedance lower than resistance. The impulse impedance of the four-leg and eight-leg counterpoise electrode in area which is high ground resistivity of 5000 ohm-meter, grounding impedance cannot be achieved because of the result of effective length. The MEG is encased with the eight-leg grounding electrode impedance can be accomplished.
dc.identifier.citation2019 IEEE Pes Gtd Grand International Conference and Exposition Asia Gtd Asia 2019, 352-355, 2019
dc.identifier.doi10.1109/GTDAsia.2019.8715911
dc.identifier.other2-s2.0-85067029369
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/9874
dc.source2019 IEEE Pes Gtd Grand International Conference and Exposition Asia Gtd Asia 2019
dc.subjectcounterpoise electrodes
dc.subjectearthing enhancing compounds
dc.subjectgrounding impedance
dc.subjectlightning impulse
dc.subjecttransmission systems
dc.titleDesign of Counterpoise Grounding Electrodes Encased with Low Resistivity Material for Transmission Towers
dc.typeConference Paper