Enhanced forced convection heat transfer of a heat exchanger tube utilizing serrated-ring turbulators
| dc.contributor.author | Pimsarn, M. | |
| dc.contributor.author | Samruaisin, P. | |
| dc.contributor.author | Eiamsa-ard, P. | |
| dc.contributor.author | Koolnapadol, N. | |
| dc.contributor.author | Promthaisong, P. | |
| dc.contributor.author | Eiamsa-ard, S. | |
| dc.date.accessioned | 2026-08-06T10:34:06Z | |
| dc.date.available | 2026-08-06T10:34:06Z | |
| dc.date.issued | 2021-12-01 | |
| dc.description.abstract | Experiments were performed to study the thermohydraulic behaviors of heating tubes equipped with serrated-ring bundles as turbulators. Their thermohydraulic characteristics are reported in terms of Nusselt numbers (Nu) and friction factors (f) as well as performance in terms of a thermohydraulic performance index (TPI) at identical pumping power. Influences of serrated-ring diagonal angles (θ = 15°, 30°, 45° and 60°), pitch ratios (PR = 6.0, 8.0 and 12.0) and Re were examined. Various geometries of serrated-ring bundles can affect the laminar sub-layer disruption, creating a reversing flow, reconnecting the separated flow to the surface, and delaying the thermal/velocity boundary layer development. These are the most important mechanisms that lead to enhanced force convection heat transfer in a fluid flow. The heat transfer rate, friction loss and TPI increased with decreasing pitch ratio (PR) and serrated-ring diagonal angle (θ ). Heat transfer rate and friction factor were increased to 2.2 and 8.8 times that of a plain tube, respectively. Over the range investigated, the highest TPI, 1.16, was found using a serrated-ring bundle having θ = 15° and PR = 6.0 at Re = 4000. | |
| dc.identifier.citation | Case Studies in Thermal Engineering, 28, 2021 | |
| dc.identifier.doi | 10.1016/j.csite.2021.101570 | |
| dc.identifier.issn | 2214157X | |
| dc.identifier.other | 2-s2.0-85117714204 | |
| dc.identifier.uri | https://dspace.kmitl.ac.th/handle/123456789/12425 | |
| dc.source | Case Studies in Thermal Engineering | |
| dc.subject | Heat transfer enhancement | |
| dc.subject | Reverse flow | |
| dc.subject | Serrated-ring bundle | |
| dc.subject | Turbulator | |
| dc.subject | Turbulence | |
| dc.title | Enhanced forced convection heat transfer of a heat exchanger tube utilizing serrated-ring turbulators | |
| dc.type | Article |