The Study of Partial Discharge Test on Service-Aged Cable Termination

dc.contributor.authorLaohapongpan, Trinai
dc.contributor.authorWiangtong, Theerayod
dc.contributor.authorKerdmanee, Sittipong
dc.contributor.authorLacharochana, Sakda
dc.contributor.authorJeenmuang, Siwakorn
dc.contributor.authorPattanadech, Norasage
dc.date.accessioned2026-08-06T10:38:34Z
dc.date.available2026-08-06T10:38:34Z
dc.date.issued2023-01-01
dc.description.abstractThis paper presents the partial discharge (PD) testing on the plug-in gas-insulated switchgear cable termination taken out of service. The shield electrodes were designed to geometrically electric field control in the area of the insulation screen edge of the cable part. The PD test of the cable termination was performed. In addition, a computed radiography technique with X-ray was also performed to evaluate the mechanical integrity of the supporting spring of the cable termination. The fatigue of the supporting spring was evidenced. Moreover, the cable termination was disassembled and re-assembled to perform the PD test again. The PD characteristics, including PD magnitude, PD inception voltage (PDIV), and phase-resolved PD (PRPD) patterns, were reported. The PD test results revealed that the PDIV was lower than the operating voltage. Besides, the PRPD patterns exhibited internal discharge inside the cable termination. From the PD test results and computed radiographic, it was assumed that they might be caused by discharge in the interface between the stress cone and epoxy insulator.
dc.identifier.citationAsia Pacific Power and Energy Engineering Conference Appeec, 2023
dc.identifier.doi10.1109/APPEEC57400.2023.10562036
dc.identifier.issn21574839
dc.identifier.other2-s2.0-85197316869
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/13642
dc.sourceAsia Pacific Power and Energy Engineering Conference Appeec
dc.subjectcable termination
dc.subjectpartial discharge
dc.subjectPDIV
dc.subjectPRPD pattern