Application of DWT and fuzzy logic algorithm for classifying simultaneous fault types

dc.contributor.authorPothisarn, C.
dc.contributor.authorNgaopitakkul, A.
dc.date.accessioned2026-08-06T10:03:25Z
dc.date.available2026-08-06T10:03:25Z
dc.date.issued2011-12-01
dc.description.abstractThis paper proposes a technique using discrete wavelet transform (DWT) and fuzzy logic for identifying types of simultaneous fault along the transmission systems. The PSCAD/EMTDC is used to simulate fault signals. The mother wavelet daubechies4 (db4) is employed to decompose high frequency component from these signals. The coefficients detail (phase A, B, C and zero sequence of post-fault current signals) of DWT at the first peak time that positive sequence current can detect fault, is performed as input variables for the proposed algorithm. The result shows that the proposed technique gives satisfactory accuracy, and will be very useful in the development of a power system protection scheme. © 2011 IEEE.
dc.identifier.citationIEEE Region 10 Annual International Conference Proceedings TENCON, 44-48, 2011
dc.identifier.doi10.1109/TENCON.2011.6129060
dc.identifier.other2-s2.0-84856852688
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/3950
dc.sourceIEEE Region 10 Annual International Conference Proceedings TENCON
dc.subjectATP/EMTP
dc.subjectdiscrete wavelet transform
dc.subjectFault Types
dc.subjectfuzzy logic
dc.subjectSimultaneous Fault
dc.titleApplication of DWT and fuzzy logic algorithm for classifying simultaneous fault types
dc.typeConference Paper

Files