Dynamic event analysis using synchronized PMUs via 220 V wall outlets

dc.contributor.authorNgamroo, Issarachai
dc.contributor.authorLappanakul, Panlert
dc.contributor.authorVoraphonpiput, Nitus
dc.contributor.authorDechanupaprittha, Sanchai
dc.contributor.authorMitani, Yasunori
dc.contributor.authorSakulrat, Jareerat
dc.date.accessioned2026-08-06T09:55:51Z
dc.date.available2026-08-06T09:55:51Z
dc.date.issued2007-12-01
dc.description.abstractThis paper presents the dynamic analysis results of a system event in Thailand power network using a wide-area monitoring system based on synchronized phasor measurement units (PMUs). The salient feature of the proposed monitoring system is the convenient installation of PMU at 220V wall power outlets. The event considering here is a 80 MW load transferring from Thailand to Malaysia systems through a weak 115 kV tieline. To perform load transferring, a synchronization between both systems is required. This causes a problem of frequency oscillation in a southern area of Thailand. Besides, this event severely excites the inter-area oscillation in a 230 kV tie-line between central and southern areas of Thailand. Analyzed results based on discrete wavelet decomposition and short-time Fourier Transform provide valuable information of the system dynamic behavior in both frequency and time domains. © 2007 RPS.
dc.identifier.citation8th International Power Engineering Conference IPEC 2007, 832-837, 2007
dc.identifier.other2-s2.0-51349100748
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/1784
dc.source8th International Power Engineering Conference IPEC 2007
dc.subjectDiscrete wavelet decomposition
dc.subjectInter-area oscillation
dc.subjectLeast-squares regression
dc.subjectShort-time Fourier Transform
dc.subjectSynchronized phasor measurement units
dc.subjectWide-area monitoring
dc.titleDynamic event analysis using synchronized PMUs via 220 V wall outlets