The Experiment of Dielectric Frequency Response of Serviced Aged Distribution Transformer

dc.contributor.authorPosrimahapoch, Purichaya
dc.contributor.authorManeerat, Noppadol
dc.contributor.authorDaengdee, Danaiwat
dc.contributor.authorJeenmuang, Siwakorn
dc.contributor.authorPannil, Pittaya
dc.contributor.authorPattanadech, Norasage
dc.date.accessioned2026-08-06T10:43:35Z
dc.date.available2026-08-06T10:43:35Z
dc.date.issued2024-01-01
dc.description.abstractOutdoor Distribution Transformers typically encounter random environments and affect moisture in any ingress ways, e.g., defective breathing, oil leakage, or human error during internal inspection, etc. Such moisture is a very important enemy of the insulation integrity of the transformer. It may cause the failure of the transformer eventually. Therefore, the condition of the transformer insulation needs to be monitored. Dielectric Frequency Response (DFR), also known as Frequency Domain Spectroscopy (FDS), and Polarization and Depolarization Current (PDC) are nondestructive tests providing efficient diagnostic for transformer insulation. The test results can be used to estimate moisture content and oil conductivity. In this paper, the dielectric investigation of a 315 kVA, 22 kV serviced aged distribution transformers, which have been retired for 6 months after being utilized for more than 20 years, was conducted. The experiment results of the DFR and the PDC tests including the investigated mineral oil characteristics (i.e., oil breakdown voltage, moisture content, and tan delta) are reported and analyzed. They should be useful to understand the condition of the transformers.
dc.identifier.citationProceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 123-126, 2024
dc.identifier.doi10.1109/ICPADM61663.2024.10750601
dc.identifier.other2-s2.0-85211089468
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/14979
dc.sourceProceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials
dc.subjectDielectric Frequency Response (DFR)
dc.subjectDistribution Transformer
dc.subjectMoisture Content
dc.subjectPolarization and Depolarization Current (PDC)
dc.titleThe Experiment of Dielectric Frequency Response of Serviced Aged Distribution Transformer