Polarization and depolarization current characteristics of thermally stressed stator bars

dc.contributor.authorPattanadech, N.
dc.contributor.authorSrichuen, N.
dc.contributor.authorWang, C.
dc.contributor.authorKaewdee, N.
dc.contributor.authorPoungpat, T.
dc.contributor.authorRaphephat, C.
dc.contributor.authorPhumipunepon, N.
dc.contributor.authorKunakorn, A.
dc.date.accessioned2026-08-06T10:24:55Z
dc.date.available2026-08-06T10:24:55Z
dc.date.issued2019-07-01
dc.description.abstractPolarization and depolarization current (PDC) measurement was used in this research to investigate the insulation integrity of stator bars. This method is non-destructive testing. This paper presents the PDC analysis of thermally stressed stator bars divided into two main groups. The first group was heated at 100^{\circ}C and the second group was heated at 130 ^{\circ}C for 36 hours. After 12, 24 and 36 hours of heating process, PDC measurement of each test specimen was performed. PDC test results including capacitance ratio and dielectric dissipation factor were analyzed and reported.
dc.identifier.citationProceedings of the 16th International Conference on Electrical Engineering Electronics Computer Telecommunications and Information Technology Ecti Con 2019, 357-360, 2019
dc.identifier.doi10.1109/ECTI-CON47248.2019.8955263
dc.identifier.other2-s2.0-85078857126
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/9957
dc.sourceProceedings of the 16th International Conference on Electrical Engineering Electronics Computer Telecommunications and Information Technology Ecti Con 2019
dc.subjectCapacitance ratio
dc.subjectDielectric dissipation factor
dc.subjectPolarization and depolarization current
dc.subjectPolarization index
dc.subjectStator winding
dc.subjectThermally stressed stator bars
dc.titlePolarization and depolarization current characteristics of thermally stressed stator bars