Development of a partial discharge testing system for potential transformers

dc.contributor.authorPrombud, T.
dc.contributor.authorKitcharoen, P.
dc.contributor.authorYutthagowith, P.
dc.date.accessioned2026-08-06T10:19:47Z
dc.date.available2026-08-06T10:19:47Z
dc.date.issued2018-04-27
dc.description.abstractIn this paper, the development of a partial discharge testing system for potential transformers (PTs) is presented. The system is composed of a low-voltage and 200-Hz power frequency converter connected with a low pass filter, a high-voltage transformer, and a conventional partial discharge detection system. The performances of the converter with three generated waveform, i.e. square wave, quasi-square wave, and unipolar pulse width modulation (PWM) are compared in terms of the DC charging voltage, the voltage difference (peak voltage/square root of 2 and rms voltage), total harmonic distortion of the output high voltage (THDv), and background noises in the partial discharge test. It is found that the unipolar PWM frequency converter provides the best performances in terms of the voltage difference, THDv, and background noise. The voltage difference and THDv are lower than 5%, and the background noise is less than 2.5 pC. In addition, the developed system has been used for the real partial test on a potential transformer in the distribution system successfully.
dc.identifier.citationProceedings of the IEEE International Conference on Industrial Technology, 2018-February, 1685-1689, 2018
dc.identifier.doi10.1109/ICIT.2018.8352435
dc.identifier.other2-s2.0-85046975120
dc.identifier.urihttps://dspace.kmitl.ac.th/handle/123456789/8529
dc.sourceProceedings of the IEEE International Conference on Industrial Technology
dc.subjectFrequency converter
dc.subjectHigh-voltage tests
dc.subjectPartial discharge
dc.subjectPotential transformer
dc.subjectPower quality
dc.titleDevelopment of a partial discharge testing system for potential transformers
dc.typeConference Paper

Files