  4. Experimental Study of the Electrical and Physiochemical Properties of Different Types of Crude Palm Oils as Dielectric Insulating Fluids in Transformers
Loading...
Thumbnail Image

Experimental Study of the Electrical and Physiochemical Properties of Different Types of Crude Palm Oils as Dielectric Insulating Fluids in Transformers

Author(s)
Muangpratoom, Pichai
Suriyasakulpong, Chinnapat
Maneerot, Sakda
Vittayakorn, Wanwilai
Pattanadech, Norasage
Date Issued
October 1, 2023
Type
Article
DOI
10.3390/su151914269
Abstract
This paper gives information on the electrical and physiochemical characteristics of six different types of palm oil compared with traditional mineral oil. We found that natural processed crude palm oil (PO-C) had a higher resistance to AC breakdown voltage than other types of palm oil, including traditional mineral oil. The results of the positive lightning impulse voltage test for PO-C were still the highest compared to other types of palm oil, including traditional mineral oil, at 58.26%. The summarised dissipation factors of all tested crude palm oils were significantly higher than those of mineral oils, which will make the palm oil less insulating, especially in PO-A palm oil (36.197%), where the values were higher than those of other oils, while mineral oil has a slightly increased dispersion factor. For relative permittivity, all palm oils were compared, and it was found that PO-C had a lower relative permittivity than the other oils. In terms of physical and chemical properties, in the moisture content test on all oils, PO-C had the percentile with the highest moisture content decrease of 58.74%. In the case of testing the surface tension value, it was found that traditional mineral oil had the highest value (48.46 m/Nm) when compared to palm oil. On the other hand, the acidity in traditional mineral oil is the lowest (0.03 mg KOH/g) compared to all palm oils. Results from studies demonstrate the possibility of using natural processed crude palm oil, or PO-C, as a replacement for traditional mineral oil. This is consistent with the results of electrical properties that show PO-C is higher than other types of palm oil and includes traditional mineral oil.
Citation
Sustainability Switzerland, 15(19), 2023
Subjects

breakdown voltage and...

dielectric loss

dielectric strength

liquid insulation

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback