Hmi implementation using radar chart for dual-loop system

Author(s)
Pongswatd, Sawai
Smerpitak, Krit
Kummool, Sart
Date Issued
August 1, 2019
Type
Article
DOI
10.24507/icicel.13.08.753
Abstract
This article presents a method to implement the Human Machine Inter-face (HMI) for providing high visibility of dual-loop system to encourage good operations and maintenance practices. The proposed method is based on the employment of radar chart to display key performance metrics of simultaneous and independent control of two identical loops for extensive event monitoring. Two level control loops utilizing two Proportional-Integral-Derivative (PID) function blocks of a single Programmable Logic Controller (PLC) are used as the case study to show the workability of the proposed HMI implementation. Each loop consists of a transmitter for measuring the controlled level an inverter for inverting the PLC output to adjust a pump speed, and a power meter form easuring the pump power consumption. The transmitter outputs from both control loops are applied to the PLC analog input module, and then separately scaled to be available to each PID block. The PLC analog output module is used to pass the PID block outputs for manipulating inlet flow rates. The performance metrics including the set point, process variable, manipulated variable, and pump power consumption of both control loops are detected and collected by the HMI/Supervisory Control and Data Acquisition (SCADA)station. All detected data of four performance metrics are represented on the axes of radar chart in real time by using the Wonder ware In Touch software. The script functions to save and load the specified data to the SQL server database are also created on the HMI/SCADA station. Experimental results confirm that the proposed HMI implementation can function correctly.
Citation
Icic Express Letters, 13(8), 753-760, 2019
Subjects

Dual-loop system

HMI

PID control

PLC

Radar chart

SCADA

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback