Repository logo
Communities & Collections
Research Outputs
Fundings & Projects
People
Statistics
New user? Click here to register.Have you forgotten your password?
  1. Home
  2. KMITL
  3. Publication
  4. Experimental studies of breakdown characteristics of a 12-kV arcing horn under a lightning impulse superimposed on AC voltage
Loading...
Thumbnail Image

Experimental studies of breakdown characteristics of a 12-kV arcing horn under a lightning impulse superimposed on AC voltage

Author(s)
Arnacha, Sunchai
Kunakorn, Anantawat
Yutthagowith, Peerawut
Tuethong, Piyapon
Date Issued
December 1, 2011
Type
Conference Paper
DOI
10.1109/APL.2011.6111104
Abstract
This paper presents the studies of breakdown characteristics of a 12-kVarcing horn under a lighting impulse superimposed on an AC power frequency voltage at various angles. The lightning impulse is superimposed on the AC power frequency voltage at a phase angle varied from 0° to 360. The 12-kV arcing horn under test has dimension and configuration according to DIN 42531 standard. The critical breakdown voltages (U b50%) with and without superposition of an impulse voltage on the AC voltage are investigated and made comparison. It is found that the statistical breakdown voltages are depended on the phase angle of the AC voltage superposed by the lightning impulse voltage. From the test results, the AC voltage affects the insulation level and it should be taken into account in an insulation design and insulation coordination. © 2011 IEEE.
Citation
2011 7th Asia Pacific International Conference on Lightning Apl2011, 205-208, 2011
Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback