  4. Partial Discharge Characteristics of a Defective MV XLPE Cable
Loading...
Thumbnail Image

Partial Discharge Characteristics of a Defective MV XLPE Cable

Author(s)
Ekasittiphong, Woraphat
Smerpitak, Krit
Tangthanam, Worasak
Jeenmuang, Siwakorn
Pattanadech, Norasage
Pongswatd, Sawai
Date Issued
January 1, 2024
Type
Conference Paper
DOI
10.1109/ICPADM61663.2024.10750726
Abstract
This paper presents the partial discharge (PD) test on a 22 kV underground cable having a simulated defect within the XLPE insulation. The defects were simulated using the nail, as the drill bits with a different drill diameter. The defect was created into the XLPE insulation layers of the underground cable. Besides, both end sides of the cable were electric field controlled. To simulate the defects for the experiment, the jacket in the middle of the cable was partially trimmed out, and the drill bits was driven through the insulation screen to the insulation layer. The diameter of the drill bits was controlled for each experiment. The PD experiment was conducted using high frequency current transformer (HFCT) sensor as an unconventional PD detection instrument. From analyzing the PD test results, a defect in the XLPE insulation causes vividly the PD inside the XLPE insulation. Consequently, the insulation gradually deteriorates undergoing the PD events. Moreover, the PD test results indicate that the larger diameter of the nail tip radius results in a higher PD magnitude than that generated by a smaller diameter.
Citation
Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 101-104, 2024
Subjects

HFCT

Partial Discharge Tes...

PD Inception Voltage

Underground Cable

XLPE

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback