  3. Publication
  4. Polarity-Dependent Dielectric Behavior of XLPO-Insulated PV Cables Under High-Voltage AC and DC Stress: Leakage Current and PRPD Analysis
Loading...
Thumbnail Image

Polarity-Dependent Dielectric Behavior of XLPO-Insulated PV Cables Under High-Voltage AC and DC Stress: Leakage Current and PRPD Analysis

Author(s)
Ruangwong, Khomsan
Pattanadech, Norasage
Pannil, Pittaya
Date Issued
January 1, 2025
Type
Conference Paper
DOI
10.1109/GTDAsia60461.2025.11313281
Abstract
This study investigates the dielectric behavior of cross-linked halogen-free polyolefin (XLPO) insulation in H1Z2Z2-K photovoltaic cables under a direct current (DC) stress of ± 999.6 V. The results indicate significant polarity-dependent responses, with insulation resistance (IR) rising from 1.61 T Ω under negative DC to 2.30 T Ω under positive DC. Furthermore, the polarization index (PI) and dielectric absorption ratio (DAR) improve from 6.73 and 2.14 to 12.78 and 2.43, respectively. The Loss Index, obtained from polarization-depolarization current (PDC) analysis, increases from 0.935 to 0.991, suggesting enhanced dielectric stability with positive bias. Additionally, the partial discharge inception and extinction voltages (PDIV and PDEV) are recorded at 8.3 kV for DC and 1.93 kV for AC, exhibiting symmetrical behavior that indicates corona and surface discharge dominance and minimal space charge retention. These findings highlight the importance of considering space charge dynamics and polarity-aware diagnostics in evaluating non-certified XLPO-insulated cables in photovoltaic applications.
Citation
IEEE Pes Gtd Conference and Exposition Asia 2025 Accelerating the Energy Transition Towards Carbon Neutrality A Sustainable Energy Future for all Gtd Asia 2025, 88-92, 2025
Subjects

Dielectric absorption...

Loss Index

Partial discharge (PD...

Polarization index (P...

Polarization-depolari...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback