Abstract

This paper proposes an equivalent circuit of grounding electrode which has validity upto a frequency range of sub-sequence stroke lightning current. The equivalent circuit is modelled by lumped and distributed parameters based on quasistatic assumption. In this study, only a grounding electrode installed horizontally is in consideration. The limitation of the uniform distributed equivalent circuit of a grounding electrode is presented. The non-uniform distributed equivalent circuit is proposed. The proposed equivalent circuits are verified by comparison of the results of ground potential rise computed by the proposed circuit, the partial element equivalent circuit method, and available experimental data. The proposed equivalent circuit can be adapted for being the models for development and design of the grounding system for lightning protection system in transmission and distribution systems in an effective way. © 2012 IEEE.

Description

Keywords

electrical transient, grounding electrodes, Grounding systems, PEEC method

Citation

Ichve 2012 2012 International Conference on High Voltage Engineering and Application, 157-161, 2012