Repository logo
Communities & Collections
Research Outputs
Fundings & Projects
People
Statistics
New user? Click here to register.Have you forgotten your password?
  1. Home
  2. KMITL
  3. Publication
  4. Additional parameters for elucidation of the dielectric behavior of stator winding in high voltage motors
Loading...
Thumbnail Image

Additional parameters for elucidation of the dielectric behavior of stator winding in high voltage motors

Author(s)
Pattanadech, Norasage
Phloymuk, Natthawut
Nimsanong, Pethai
Srinangyam, Chissanupong
Jeenmuang, Siwakorn
Bunlaksananusorn, Chanin
Date Issued
November 1, 2022
Type
Article
DOI
10.1016/j.egyr.2022.02.282
Abstract
This paper proposes additional parameters for describing the dielectric behaviors of the stator winding in high voltage motors used in coal power plants. The on-site MV induction motors with indirect air-cooling rated 6.6 kV, 260 to 3091 kW, were investigated. These motors were installed in different parts of the plants and operated under different conditions. Therefore, the stator winding conditions of such motors were different. The integral insulation conditions of stator winding were examined by analysis of the dielectric response. Whereas the local insulation conditions of the stator winding, the so-called weak spot condition, were examined by analysis of the off-line PD test results. To deeply understand the dielectric behavior of such stator windings, a proposed simplified equivalent circuit for modeling the insulation system of the stator winding was introduced and constructed, which aimed to distinguish the dielectric behavior into conductivity, polarization, and ionization mechanisms. The additionally parameters, i.e., the minor capacitance (Ci), the minor resistance (Ri), the dc resistance (Rdc), the minor capacitance at defect site (CPD), the conductivity loss factor (Tan δσ), and the polarization loss factor (Tan δpol) were estimated and proposed. It can be concluded that the proposed additional parameters are a valuable tool for assessing the insulation condition, which reduces the ambiguity in the interpretation of the insulation test results and is suitable for monitoring insulation conditions over the service life of the high voltage motors.
Citation
Energy Reports, 8, 3629-3635, 2022
Subjects

Large motor

Loss factors

PD analysis

PDC analysis

Stator winding

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback