Heat transfer in turbulent tube flow inserted with loose-fit multi-channel twisted tapes as swirl generators

Author(s)
Kunlabud, Suttisak
Chuwattanakul, Varesa
Kongkaitpaiboon, Vichan
Promthaisong, Pitak
Eiamsa-ard, Smith
Date Issued
November 1, 2017
Type
Letter
DOI
10.1016/j.taml.2017.11.011
Abstract
Heat transfer and flow behaviors in three-dimensional circular tubes with loose-fit multiple channel twisted tapes were numerically studied. The investigation was examined for Reynolds numbers (Re) ranging from 5000 to 15,000, by using air as testing fluid. Effects of the multiple channel number (N=2,3, and 4), clearance ratio (CR=0.0, 0.025, 0.05, and 0.075) on heat transfer enhancement and flow friction were examined. The numerical results indicate that the tubes with loose-fit multiple channel twisted tapes perform higher heat transfer rates than the plain tube. The enhanced heat transfer rate is escorted with larger pressure drop. Both heat transfer and pressure drop increase with increasing multiple channel number (N) and decreasing clearance ratio (CR). Heat transfer augmented by the loose-fit multiple channel twisted tape with N=4 is higher than those enhanced by the ones with N=2 and 3 by around 9.5–17.8% and 5.8–7.8%, respectively. In addition, the loose-fit multiple channel twisted tapes with clearance ratio of 0.025, 0.05, and 0.075 give lower heat transfer rates than the one with CR=0.0 by around 8.4%, 17.5%, and 28.8%, respectively.
Citation
Theoretical and Applied Mechanics Letters, 7(6), 372-378, 2017
Subjects

Heat transfer

Heat transfer enhance...

Loose-fit multiple ch...

Swirling flow

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback