Publication: Failure analysis of dielectric of low voltage power capacitors due to related harmonic resonance effects
Loading...
Date
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
This paper presents an investigation on the failure of low voltage power capacitors used in the textile industrial located on Thailand. The causes of the failure as well as the failure mechanisms of the dielectric used as the insulation of such capacitors are analyzed. It is found that the harmonic resonance can increase the current flowing through the capacitors. This result in the extra heat, generated inside the dielectric, which exceeds the level under the normal operation. Such heat results in the increase of the partial discharge inside the capacitors. This can eventually lead to the reduction of the lifetime of the capacitors.
Description
Keywords
Capacitor, Failure analysis, Harmonics resonance
Citation