  4. The Development of An Adjustable Low-pass Filter for A Partial Discharge Detection System under Testing with The Power Frequency Converter
Loading...
Thumbnail Image

The Development of An Adjustable Low-pass Filter for A Partial Discharge Detection System under Testing with The Power Frequency Converter

Author(s)
Leelachariyakul, Banyat
Yutthagowith, Peerawut
Date Issued
September 1, 2019
Type
Conference Paper
DOI
10.1109/UPEC.2019.8893586
Abstract
In this paper presents the partial discharge detection system based on the power frequency converter as a low-voltage source and an adjustable low-pass filter which is constructed from variable inductor and fixed capacitor. The inductance is able to vary in the range of 8.69 mH to 18.82 mH. This adjustable low-pass filter circuit in partial discharge detection system is able to filter the undesired harmonic voltage and also reduce background noise. It is compatible with partial discharge detection system for high voltage equipment. The background noise of the commercial partial discharge detection system and the total harmonic distortion (THDv) of the testing voltage are improved. The results show that this low-pass filter that had been designed and constructed is capable for filtering the noise from a power frequency converter in the PD test and the undesired harmonic voltage sufficiently. The quality of the testing high voltage is good and sufficient for testing equipment such as potential transformers. Thus, application of this particular adjustable low-pass filter with variable cut-off frequency to the power frequency converter is a promising approach for generation of an AC sinusoidal voltage for the partial discharge detection system.
Citation
2019 54th International Universities Power Engineering Conference Upec 2019 Proceedings, 2019
Subjects

adjustable low-pass f...

background noise

high-voltage tests

partial discharge

power frequency conve...

total harmonic distor...

variable inductor

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback