Repository logo
Communities & Collections
Research Outputs
Fundings & Projects
People
Statistics
New user? Click here to register.Have you forgotten your password?
  1. Home
  2. KMITL
  3. Publication
  4. The Experiment of VLF Tanδ on Service-aged MV Underground Cable
Loading...
Thumbnail Image

The Experiment of VLF Tanδ on Service-aged MV Underground Cable

Author(s)
Tangthanam, Worasak
Bunlaksananusorn, Chanin
Suksawat, Dusit
Udomluksananon, Patt
Jeenmuang, Siwakorn
Pattanadech, Norasage
Date Issued
January 1, 2024
Type
Conference Paper
DOI
10.1109/ICPADM61663.2024.10750629
Abstract
This paper presents the service-aged MV underground cable experiment using very low frequency (VLF) testing. The underground cables in this experiment have been utilized in service for more than 10 years and subjected to TEAM stresses, particularly with moisture, throughout the service time. So, the effect of moisture leads these cables to bad condition. The cables under the experiments are both service-aged and unaged. These cables were prepared the same by peeling both end sides of the cables and were terminated with high voltage insulating tape. The VLF test combined with the tangent delta (tanδ) measurement, according to IEEE Std. 400.2-2013 was performed to assess the condition of these cables and compare them with the unaged cable. The test results revealed that according to IEEE standard 400.2-2013, the service-aged underground cables were assessed in Action Required criteria. Still, the unaged underground cable was assessed in the Further Study Required criteria. Moreover, the tanδ values from service-aged underground cables have significant differences, with service-aged underground cables having higher values than unaged cables. Besides, the variation of tanδ data samples at each test voltage level from some underground cables shows a decreasing trend at 1.0U0 and 1.5U0. Nevertheless, the test voltage at 0.5U0 shows the constant trend of tanδ samples. This analyzed result can indicate that the insulation condition has humidity inside the cable insulation.
Citation
Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 158-161, 2024
Subjects

MV underground cable

service-aged conditio...

tangent delta

very low frequency te...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback