The Experiment of Dielectric Frequency Response of Serviced Aged Distribution Transformer

Author(s)
Posrimahapoch, Purichaya
Maneerat, Noppadol
Daengdee, Danaiwat
Jeenmuang, Siwakorn
Pannil, Pittaya
Pattanadech, Norasage
Date Issued
January 1, 2024
Type
Conference Paper
DOI
10.1109/ICPADM61663.2024.10750601
Abstract
Outdoor Distribution Transformers typically encounter random environments and affect moisture in any ingress ways, e.g., defective breathing, oil leakage, or human error during internal inspection, etc. Such moisture is a very important enemy of the insulation integrity of the transformer. It may cause the failure of the transformer eventually. Therefore, the condition of the transformer insulation needs to be monitored. Dielectric Frequency Response (DFR), also known as Frequency Domain Spectroscopy (FDS), and Polarization and Depolarization Current (PDC) are nondestructive tests providing efficient diagnostic for transformer insulation. The test results can be used to estimate moisture content and oil conductivity. In this paper, the dielectric investigation of a 315 kVA, 22 kV serviced aged distribution transformers, which have been retired for 6 months after being utilized for more than 20 years, was conducted. The experiment results of the DFR and the PDC tests including the investigated mineral oil characteristics (i.e., oil breakdown voltage, moisture content, and tan delta) are reported and analyzed. They should be useful to understand the condition of the transformers.
Citation
Proceedings of the IEEE International Conference on Properties and Applications of Dielectric Materials, 123-126, 2024
Subjects

Dielectric Frequency ...

Distribution Transfor...

Moisture Content

Polarization and Depo...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback