Discriminating among inrush current, external fault and internalwinding fault using coefficient of DWT
Loading...
Date
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
This paper proposes a technique for discriminating among inrush current, external fault and internal winding fault of three-phase two-winding transformer which variations of coefficients of high frequency component obtained from DWT of differential current are analyzed. The maximum coefficient details of DWT are performed as comparison indicator. Various cases based on Thailand electricity transmission and distribution systems are studied to verify the validity of the proposed algorithm. Results show that the proposed technique has good accuracy in the considered system.
Description
Keywords
Discrete wavelet transforms, External fault, Internal fault, Transformer
Citation