  4. Simulation analysis of the switching of 230kV substation shunt capacitor banks with a 6% series reactor for limiting transient inrush currents and oscillation overvoltage
Loading...
Thumbnail Image

Simulation analysis of the switching of 230kV substation shunt capacitor banks with a 6% series reactor for limiting transient inrush currents and oscillation overvoltage

Author(s)
Patcharoen, Theerasak
Ngaopitakkul, Atthapol
Pothisarn, Chaichan
Leelajindakrairerk, Monthon
Date Issued
June 1, 2018
Type
Article
DOI
10.1007/s00202-017-0516-4
Abstract
This paper presents the simulation and investigation of switching large shunt capacitor banks in a 230kV Thailand substation system. Simulations are performed using PSCAD/EMTDC to determine the peak of the transient inrush currents, the oscillation overvoltage and the frequency of the inrush current. The inrush current is generated by energizing the 4 × 72 Mvar, 230kV shunt capacitor banks. The purpose is to observe and investigate the behaviour of transient inrush currents and oscillation overvoltages to ensure the safe and successful operation of shunt capacitor banks. The methodology of inrush current transient analysis and transient reduction control was studied. The proposed method for controlling system transients during capacitor energization is through the use of a switching shunt capacitor bank with a series 6% reactor. The simulation cases for transient mitigation are numerically conducted for six different cases: a base case, with a pre-insertion resistor, with a pre-insertion inductor, with a current-limiting reactor, with a series 6% reactor and using synchronous closing control. The effects of parameters such as the sizing of the current-limiting reactor, the capacitor bank rating and the short-circuit impedance of the system are investigated. The simulation results demonstrate that the switching shunt capacitor bank with a series 6% reactor is effective in reducing the high transient inrush currents and oscillation overvoltages.
Citation
Electrical Engineering, 100(2), 435-459, 2018
Subjects

6% reactor

Back-to-back capacito...

Current-limiting reac...

Inrush current

Oscillation overvolta...

Shunt capacitor bank

Switching transients

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback