Abstract
This paper represents the condition assessment of service-aged 22 kV XLPE insulated underground cables. From the investigation, the water trees were detected in the insulation layer. The visual inspection of underground cables reveals the presence of copper carbonate contaminated on the copper tape layer. Some underground cables have the discontinuity of the copper tape layer. To evaluate the insulation condition of the underground cables, the polarization and depolarization current (PDC) measurements were performed on both the service-aged and the new (or unused) cables. The underground cables to experiment with the length of insulation screen equal to 1 m were prepared. In this research, the PDC measurements were performed on different aspects, i.e., the testing voltages (600 V, 800 V, and 1000 V), the testing positions, the effect of the discontinuity of the copper tape layer which occurred during service, the influence of the presence of copper carbonate, and the influence of water trees in XLPE cables. The dielectric response of the underground cables by using polarization and depolarization current measurements can diagnose the problems in service-aged underground cables, but this paper needs more test data for accurate interpretation.
Citation
2022 9th International Conference on Condition Monitoring and Diagnosis Cmd 2022, 127-132, 2022
Subjects

PDC measurements

Polarization and depo...

Water trees

XLPE underground cabl...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback