Repository logo
Communities & Collections
Research Outputs
Fundings & Projects
People
Statistics
New user? Click here to register.Have you forgotten your password?
  1. Home
  2. KMITL
  3. Publication
  4. PFD analysis of LNG fuel gas supply system for improving combined-cycle power plant safety
Loading...
Thumbnail Image

PFD analysis of LNG fuel gas supply system for improving combined-cycle power plant safety

Author(s)
Thepmanee, Teerawat
Julsereewong, Amphawan
Pongswatd, Sawai
Date Issued
April 1, 2022
Type
Article
DOI
10.1016/j.egyr.2021.11.188
Abstract
In order to determine an unavailability of each safety function subsystem that influences on an overall unavailability of entire protection system for safety analysis and enhancement, a modeling is required. This article presents a safety system modeling to evaluate the detected–undetected failures and repairable behaviors of each safety function subsystem in the studied fuel gas supply system (FGSS), which is utilized in a combined-cycle power plant. The proposed modeling deals with probability of failure on demand (PFD) analysis for calculation of the unavailability of three safety function subsystems, which are gas analytical subsystem (GAS), fuel gas controller subsystem (FGC), and shutdown valve subsystem (SDV). The interested GAS includes two different groups of gas analyzers in 2-out-of-2 (2oo2) voting scheme, when using three gas analyzers in each group in 2-out-of-3 and diagnosis (2oo3D) voting scheme. The interested FGC consists of two controllers in 2oo2 voting scheme, when the structure of each controller is in 1-out-of-1 and diagnosis (1oo1D) voting scheme. The interested SDV consists of two shutdown valves, which are installed in 1-out-of-2 (1oo2) voting scheme. The reliability block diagram is utilized for representative of combination of all three safety function subsystems, and the fault tree is utilized for calculation of PFD unavailability of each safety function subsystem. As the results obtained from the proposed safety function modeling, the influence of three safety function subsystems on the total unavailability of the FGSS is described. In addition, an example of the proposed modeling application to provide two guidelines for effective engineering design and operation is also presented. The first is a guideline to implement an effective human machine interface (HMI) at an operator workstation for real-time monitoring of the studied FGSS in the presence of failures that can be automatically detected by device diagnosis. The latter is a guideline to maintain and troubleshoot the failures that can be revealed by proof test. Based on diagnostic information and proof test results, operation and maintenance savings can be achieved.
Citation
Energy Reports, 8, 684-690, 2022
Subjects

Combined-cycle power ...

Fault tree

Fuel gas supply

Probability failure o...

Reliability​ block di...

Unavailability

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback