  4. Very Small Power Plant Transformer Without and With Installation of Neutral Ground Resistance on Relay Operation
Loading...
Thumbnail Image

Very Small Power Plant Transformer Without and With Installation of Neutral Ground Resistance on Relay Operation

Author(s)
Pothisarn, Chaichan
Chiradeja, Pathomthat
Yoomak, Suntiti
Srisuksai, Panu
Ngaopitakkul, Atthapol
Phannil, Natthanon
Date Issued
January 1, 2024
Type
Article
DOI
10.1109/TIA.2024.3427058
Abstract
In this study, a double-feeder 22 kV distribution system connected to a very small power plant (VSPP) was simulated in the PowerFactory DIgSILENT program. A neutral ground resistance (NGR) was introduced to reduce a ground fault current from the VSPP, extend the relay operating time to the delay range, and reduce undesired trip of non-faulty feeder that VSPP connected. Thus, the overcurrent protection relay was simulated to analyze working patterns during faults. Three types of VSPP transformer NGR installations were considered: VSPP without NGR, VSPP with a Bisection method approach, and VSPP with the proposed symmetrical component calculation approach. Moreover, this study analyzed the effect of overvoltage on the distribution system with the proposed systematic component calculation approach under fault conditions. The result from the case study indicated that the NGR installation with the proposed approach can reduce the fault current and shift delay time of the protection device to avoid maloperation.
Citation
IEEE Transactions on Industry Applications, 60(5), 7693-7701, 2024
Subjects

Distributed generatio...

neutral ground resist...

overcurrent protectio...

single-phase fault

very small power plan...

Metrics
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your Institution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Accessibility settings
  • Privacy policy
  • End User Agreement
  • Send Feedback